EPSCO Arc Flash Study Recommendations & Red Flags

Technical Documents: RECOMMENDATIONS

by | Feb 4, 2018 | Uncategorized

As part of your full arc flash report, EPSCO provides you with recommendations and red flags that may impact your facility. While we don’t provide most of the services needed to resolve these red flags, one of EPSCO’s field engineers can provide you with guidance on local contractors.

Device Existing Recommended Recommendation
(800P) MAIN-PAINT PLANT 68 cals/cm² <8 cals/cm² Must install upstream protective device to lower incident energy.
(801P) MAIN SERVICE PAINT 68 cals/cm² <8 cals/cm² Unable to lower due to nuisance tripping with downstream device.
(819P) PANEL-DS-1 37 cals/cm² <8 cals/cm² Recommend installing integral trip unit with LTPU, LTD, STPU, STD, INST.
(802P) PANEL-DS3 19 cals/cm² 1.6 cals/cm² By lowering the feeder fuse from 600amp to 400amps, it will lower the incident energy level from 19 to 1.6 cals/cm².
BUS BAR-7 BUS PLUGS 27 cals/cm² <1.2 cals/cm² By lowering the INST setting on the feeder breaker from 4 to 3 it will lower the incident energy from 27 cals/cm² to 0.41.